Type
|
Gutor WxW 1000 (single phase)
|
Gutor WxW 3000 (three phase)
|
Ratings
|
5-200 kVA (Higher ratings upon request)
|
10-220 kVA (Higher ratings upon request))
|
Operating temperature
|
- 10 to +40 °C (max. 55 °C on request)
|
Allowable air humidity
|
< 95 % (non condensing)
|
Noise level
|
60 – 75 dBA (depending on rating)
|
Communication protocols
|
Modbus RTU, Webpage (HTTP), Modbus TCP, IEC 61850 (others on request)
|
Input
|
Voltage
|
110 / 125 / 220 / 400 VDC
|
Voltage tolerance
|
''+20/-15%
|
Output
|
Voltage
|
220 / 230 / 240V (others on request)
|
380 / 400 / 415V (others on request)
|
Tolerance (static)
|
+/- 1 %
|
Frequency stability (free running)
|
< 0.01 %
|
Efficiency
|
up to 93% depending on type
|
Distortion
|
linear load: ≤ 3 % / non-linear load: ≤ 5 %
|
Overload inverter
|
200% / 50-100 ms, 150% / 1 min, 125% /10 min
|
Overload bypass
|
1000 % / 100 ms
|