Type
|
Gutor PXP 1000 (single phase)
|
Gutor PXP 3000 (three phase)
|
Ratings
|
5,10, 15, 20, 30, 40, 50, 60, 80, 100, 120, 140, 160 kVA(Higher ratings upon request)
|
Operating temperature
|
- 10 to +40 °C (max. 55 °C on request)
|
Allowable air humidity
|
< 95 % (non condensing)
|
Noise level
|
55 – 65 dBA (depending on rating)
|
Communication protocols
|
Modbus RTU (4-Wire), Modbus TCP, Webpage (HTTP), SNMP, IEC 61850
|
Altitude above sea level
|
< 1000 m without load de-rating
|
Input
|
Rectifier
|
PFC technology (less than 5 % distortion back to line power)
|
Voltage
|
3 x 380 / 400 / 415V (other voltages on request)
|
Voltage tolerance
|
''+/- 10% for DC in tolerance
-15/+10% for function
|
Battery circuit
|
Nominal voltage
|
400VDC
|
Applicable batteries
|
Lead Acid, Nickel Cadmium
|
Output
|
Voltage
|
220 / 230 / 240V (others on request)
|
380 / 400 / 415V (others on request)
|
Tolerance (static)
|
+/- 1 %
|
Frequency stability
(free running)
|
< 0.01 %
|
Efficiency
|
up to 91% depending on type
|
Distortion
|
linear load: ≤ 3 % / non-linear load: ≤ 5 %
|
Overload inverter
|
200% / 50-100 ms, 150% / 1 min, 125% /10 min
|
Overload bypass
|
1000 % / 100 ms, 150 % / 1 min, 125 % / 10 min
|